Pneumatic Valve Positioner
Non-standard controller output: The positioner is used to operate a valve with 3-15 psi spring range when controller signal is other than 3 –15 psi.
Downloads
Specification DocumentDesign Features
- Non-standard controller output
- Non-standard actuator spring range
- Remote valve location
- Split range
- Improves all performance
About Pneumatic Valve Positioner
Non-standard controller output
The positioner is used to operate a valve with 3-15 psi spring range when controller signal is other than 3 –15 psi.
Non-standard actuator spring range
The positioner is used to operate valves having non standard actuator spring ranges by controllers having the standard 3-15 psi signal pressure.
Remote valve location
When air operated control valves are located far from control instrument, positioners will reduce lag, thereby speeding up valve operation.
Split range
Some processes require the dual or sequential operation of two to three control valves by a single controller with a 3-15 psi output signal range.
Improves all performance
When process lags necessitate the use of wide controller proportional band, the positioner provides an exact means of making the control valve responsive to infinitely small changes in controller output pressure.
Product Specifications
Model | PVP-1 Single Acting - Direct Action, PVP-2 Single Acting - Reverse Action, PVP-3 Double Acting - Direct Action |
Supply Connection | 1 /4” NPT (F) |
Supply Air Pressure | 1.4 To 3.5 kg/cm2 (Standard.) 5.0 kg/cm2 (Maximum) |
Input | 0.2 – 1.0 kg/cm2 (Standard) |
Hysteresis | Within ± 1% of FS |
Linearity | Within ± 1% of FS |
Dead Band | Within 0.1% of FS |
Stroke Speed (max) | 10mm/sec |
Stroke | 14 mm to 100mm |
Air Consumption | 7.0 NL / Min (Normal.) |
Air Flow Capacity | 200 NL / Min (Maximum.) |
Housing | Die cast aluminum to LM – 6 |
Internals & Linkage | AISI 304 |
Diaphragm | Nitrile / Neoprene with nylon fabric reinforcement |